BG-10 series pull stations — manufacturer safety advisory

Honeywell says a seal around the alarm switch in BG-10 series pull stations manufactured from 1992 through 2010 can deteriorate and prevent the station from signaling when pulled.

What technicians may encounter

The BG-10 family was sold under multiple Honeywell-related and legacy brands, including NOTIFIER and Fire-Lite. These manual stations remain common in older buildings.

Known issue

Honeywell's safety information says the seal around the alarm switch can deteriorate over time. If the seal interferes with the switch, pulling the station may not transmit the intended alarm signal.

What Honeywell recommends

Honeywell strongly recommends replacing affected BG-10 series pull stations with the appropriate BG-12 series replacement. Treat this as a manufacturer safety advisory and replacement recommendation, not as a blanket statement that every red pull station is recalled.

Field takeaway

Identify the exact model, firmware, and date information before deciding the equipment is affected. Document what you find and follow the official source and your company's approved impairment/replacement process.

Official source

Always verify the current manufacturer or government notice before acting.