Elevator Recall Fire Alarm Interfaces Explained

A practical overview of lobby detection, primary and alternate recall, machine-room functions, shunt trip, hat-light indication, and test coordination.

What this guide helps you do

  • Understand the approved sequence before testing
  • Separate recall, shunt trip, and visual indication functions
  • Coordinate with the elevator contractor
  • Document each initiating device and resulting action

Field perspective

Where this usually goes wrong

Elevator recall problems cross trade boundaries. The fastest troubleshooting comes from separating what the fire alarm system is commanding from what the elevator controller actually receives and does.

Treat elevator recall as a coordinated system

Elevator emergency operation involves the fire alarm system, elevator controller, power equipment, sprinkler supervision, and sometimes a shunt-trip disconnect. No single trade controls the entire sequence. Testing must be coordinated with the building representative and qualified elevator personnel.

Primary and alternate recall

Smoke detection at designated elevator lobbies and related spaces may initiate recall. The selected floor and alternate floor are determined by the approved design. The fire alarm system typically provides dry contacts or addressable relay outputs to the elevator controller, while the elevator equipment performs the actual car movement and door operation.

Verify the correct detector label, relay assignment, and recall floor. A relay click alone does not prove the elevator responded correctly.

Machine room and hoistway functions

Detection in a machine room, control room, machinery space, or hoistway may have a different effect from lobby detection, including alternate recall or firefighter visual indication. The exact response depends on the adopted code, sprinkler arrangement, elevator equipment, and approved sequence.

Shunt trip is a separate function

Where shunt trip is used, heat detection or another approved initiating condition may disconnect elevator power before sprinkler water creates an electrical hazard. The sequence often includes a time relationship between initiating devices, shunt-trip power supervision, and elevator recall. Never test shunt trip casually; it can trap equipment, damage drives, or require elevator service to restore.

Hat-light or firefighter visual indication

A dedicated visual indication may warn firefighters that detection in an elevator machine space or hoistway has operated. Verify the correct initiating devices, relay logic, and annunciation. Do not assume that every machine-room detector should produce the same response.

Plan the functional test

Review the matrix, drawings, point list, and elevator interface wiring. Place monitoring on test, coordinate car availability, and confirm who will observe the elevator response. Test each required initiating location individually, verify recall floor, door operation, visual indicators, relay restoration, and panel reset.

Record any mismatch between the approved sequence and actual operation. Do not reprogram interfaces in the field without authorization and updated documentation.

Common mistakes to avoid

  • Changing fire alarm programming before proving the interface relay state
  • Testing recall without coordinating with elevator personnel and site management
  • Treating shunt trip, recall, and hat-light functions as the same sequence

Field checklist

  1. Review the approved sequence and elevator interface drawings
  2. Coordinate with qualified elevator personnel
  3. Test primary and alternate recall separately
  4. Verify machine-room and hoistway indications
  5. Treat shunt trip as a controlled high-risk test
  6. Confirm all relays restore after reset
  7. Document each device-to-function result

What to verify before you act

Use this article to organize the field problem, then verify the requirement or permitted method in the documents that govern the job:

  • The adopted fire alarm and building/fire code editions for the project
  • The manufacturer installation, service, and compatibility documentation
  • Approved drawings, sequence of operations, project specifications, and AHJ direction

Important limitation

This guide is a field-oriented starting point, not a substitute for the adopted code, approved drawings, project specifications, manufacturer instructions, site safety procedures, or the authority having jurisdiction. Do not bypass a listed protection feature or leave a required system impaired without following the approved impairment process.